有(you)(you)(you)的管道(dao)設(she)計人員因不清(qing)楚靜電(dian)(dian)接(jie)地范圍(wei)而(er)引起設(she)計事故,因此著重講述。我國管道(dao)靜電(dian)(dian)接(jie)地和跨接(jie)相(xiang)關標(biao)準規范有(you)(you)(you)GB12158《防止靜電(dian)(dian)事故通(tong)用導(dao)則(ze)》、HG/T 20675《化工(gong)企(qi)業(ye)(ye)靜電(dian)(dian)接(jie)地設(she)計規程》、SH/T 3097《石油化工(gong)靜電(dian)(dian)接(jie)地設(she)計規范》等(deng),GB 50235《工(gong)業(ye)(ye)金屬(shu)管道(dao)工(gong)程施工(gong)規范》等(deng)規范也有(you)(you)(you)專門的章節對管道(dao)靜電(dian)(dian)接(jie)地實施作出規定。ASME、PIP等(deng)國外標(biao)準規范也有(you)(you)(you)具(ju)體規定,國內外一(yi)些大(da)型公司和工(gong)程建設(she)單位,對管道(dao)靜電(dian)(dian)接(jie)地設(she)計有(you)(you)(you)企(qi)業(ye)(ye)級的規定。


   ①. 位于爆炸(zha)(zha)和火(huo)(huo)災(zai)(zai)危(wei)險區內(nei)(nei)的(de)(de)管道應進行靜(jing)電接地(di)。在爆炸(zha)(zha)和火(huo)(huo)災(zai)(zai)危(wei)險區內(nei)(nei),可(ke)能存在可(ke)燃(ran)(ran)(ran)氣體(ti)和可(ke)燃(ran)(ran)(ran)粉塵積聚,如果產生電火(huo)(huo)花(hua),可(ke)能引(yin)起火(huo)(huo)災(zai)(zai)或爆炸(zha)(zha)事故(gu)。為了防(fang)止在電氣設(she)施(shi)使用過(guo)程中產生電火(huo)(huo)花(hua),引(yin)燃(ran)(ran)(ran)或引(yin)爆可(ke)燃(ran)(ran)(ran)氣體(ti)或可(ke)燃(ran)(ran)(ran)粉塵,爆炸(zha)(zha)和火(huo)(huo)災(zai)(zai)危(wei)險區內(nei)(nei)的(de)(de)強(qiang)、弱電設(she)施(shi)均需要選用防(fang)爆型(xing)。


   ②. 氧(yang)氣(qi)管道應進行靜電接(jie)地。氧(yang)氣(qi)是(shi)一種特(te)殊的介(jie)質,其本身不燃燒,卻是(shi)強氧(yang)化劑,在(zai)純氧(yang)的環境中,鋼管會被點燃。因此(ci)雖然氧(yang)氣(qi)不屬于可燃介(jie)質,但純氧(yang)管道必須良好接(jie)地。


   ③. 氣固管(guan)道(dao)應進行(xing)靜(jing)電接地(di)。氣固管(guan)道(dao)在運行(xing)過程中會(hui)產生大量靜(jing)電,必(bi)須保證管(guan)道(dao)良好接地(di),防止大量靜(jing)電集聚。


   ④. 平行(xing)敷(fu)(fu)設(she)的管(guan)道(dao),凈距小于100mm時,應每隔20m,設(she)置(zhi)靜電跨接。近(jin)距離平行(xing)敷(fu)(fu)設(she)的管(guan)廊(lang),為保證兩根管(guan)道(dao)等電位,需要每隔20m設(she)置(zhi)跨接。


   ⑤. 管道進(jin)出(chu)裝置(zhi)界區處應進(jin)行靜(jing)電(dian)(dian)接地,防止界外管道和裝置(zhi)內(nei)管道間電(dian)(dian)荷的相互轉移。