①. 熱(re)水熱(re)力網管(guan)道地下敷(fu)設時(shi),應(ying)優先采(cai)(cai)用(yong)(yong)直埋(mai)敷(fu)設;熱(re)水或蒸(zheng)汽管(guan)道采(cai)(cai)用(yong)(yong)管(guan)溝(gou)敷(fu)設時(shi),應(ying)首選不(bu)通(tong)(tong)行管(guan)溝(gou)敷(fu)設;穿越不(bu)允許開挖檢修的地段時(shi),應(ying)采(cai)(cai)用(yong)(yong)通(tong)(tong)行管(guan)溝(gou)敷(fu)設;當采(cai)(cai)用(yong)(yong)通(tong)(tong)行管(guan)溝(gou)困難時(shi),可采(cai)(cai)用(yong)(yong)半通(tong)(tong)行管(guan)溝(gou)敷(fu)設。蒸(zheng)汽管(guan)道采(cai)(cai)用(yong)(yong)管(guan)溝(gou)敷(fu)設困難時(shi),可采(cai)(cai)用(yong)(yong)保溫(wen)性(xing)能(neng)良好、防水性(xing)能(neng)可靠、保護管(guan)耐腐蝕(shi)的預制保溫(wen)管(guan)直埋(mai)敷(fu)設,其設計壽命應(ying)不(bu)低于(yu)25年。


 ②. 河(he)(he)(he)底敷(fu)(fu)設管(guan)道(dao)必須(xu)遠(yuan)離淺灘、錨地,選擇在(zai)較深的穩(wen)(wen)定(ding)河(he)(he)(he)段,埋設深度應(ying)按不妨礙河(he)(he)(he)道(dao)整治和(he)保證管(guan)道(dao)安全的原則確定(ding)。對(dui)(dui)于一至五級航道(dao)河(he)(he)(he)流,管(guan)道(dao)(管(guan)溝)應(ying)敷(fu)(fu)設在(zai)航道(dao)底設計標高2m以(yi)下,對(dui)(dui)于其他河(he)(he)(he)流,管(guan)道(dao)(管(guan)溝)應(ying)敷(fu)(fu)設在(zai)穩(wen)(wen)定(ding)河(he)(he)(he)底1m以(yi)下。對(dui)(dui)于灌溉(gai)渠道(dao),管(guan)道(dao)(管(guan)溝)應(ying)敷(fu)(fu)設在(zai)渠底設計標高0.5m以(yi)下。管(guan)溝敷(fu)(fu)設或直埋敷(fu)(fu)設管(guan)道(dao)河(he)(he)(he)底敷(fu)(fu)設時,應(ying)進行(xing)抗(kang)浮(fu)計算。


 ③. 熱力網管道(dao)同(tong)河流、鐵(tie)路、公路等交(jiao)(jiao)叉(cha)時(shi)應垂直(zhi)相交(jiao)(jiao)。特殊情(qing)況下(xia),管道(dao)與鐵(tie)路或(huo)地下(xia)鐵(tie)路交(jiao)(jiao)叉(cha)角度不(bu)得(de)小(xiao)于(yu)60°;管道(dao)與河流或(huo)公路交(jiao)(jiao)叉(cha)角度不(bu)得(de)小(xiao)于(yu)45°。


 ④. 地下(xia)敷(fu)設管(guan)(guan)道(dao)(dao)與鐵路或不允許開挖的公路交叉,交叉段的一(yi)側留有(you)足夠(gou)的抽管(guan)(guan)檢修地段時(shi),可采用(yong)套(tao)管(guan)(guan)敷(fu)設。套(tao)管(guan)(guan)敷(fu)設時(shi),套(tao)管(guan)(guan)內不應(ying)(ying)(ying)采用(yong)填充式保(bao)溫(wen),管(guan)(guan)道(dao)(dao)保(bao)溫(wen)層(ceng)與套(tao)管(guan)(guan)間應(ying)(ying)(ying)留有(you)不小于50mm的空(kong)隙。套(tao)管(guan)(guan)內的管(guan)(guan)道(dao)(dao)及其他鋼部件應(ying)(ying)(ying)采取加強防(fang)腐措施(shi)。采用(yong)鋼套(tao)管(guan)(guan)時(shi),套(tao)管(guan)(guan)內、外(wai)表面均應(ying)(ying)(ying)進(jin)行防(fang)腐處(chu)理。


 ⑤. 地下(xia)敷設熱力網(wang)管(guan)道(dao)(dao)和管(guan)溝(gou)應設坡(po)(po)度,其坡(po)(po)度不小于0.002。進入建筑物(wu)的(de)管(guan)道(dao)(dao)應坡(po)(po)向干管(guan)。地上敷設的(de)管(guan)道(dao)(dao)可不設坡(po)(po)度。


 ⑥. 地下敷設熱(re)力(li)網管道的覆土深度應符合下列規定。


   a. 管溝蓋板或檢查室蓋板覆土深(shen)度不應(ying)小于0.2m。


   b. 直(zhi)埋敷設管道的(de)(de)最小覆土(tu)深度應考慮土(tu)壤(rang)和地(di)面活荷載對管道強度的(de)(de)影(ying)響(xiang)并保證管道不發生(sheng)縱向失穩(wen)。具體規定應按CJJ/T 81《城鎮直(zhi)埋供熱管道工程技(ji)術規程》規定執(zhi)行。


 ⑦. 燃氣管(guan)(guan)(guan)道不(bu)(bu)得進入熱(re)(re)力網(wang)管(guan)(guan)(guan)溝(gou)。當自來(lai)水管(guan)(guan)(guan)道、排水管(guan)(guan)(guan)道或(huo)電纜與(yu)熱(re)(re)力網(wang)管(guan)(guan)(guan)道交叉必(bi)須穿入熱(re)(re)力網(wang)管(guan)(guan)(guan)溝(gou)時(shi),應加套管(guan)(guan)(guan)或(huo)用厚度不(bu)(bu)小(xiao)于100mm的混凝土防護層(ceng)與(yu)管(guan)(guan)(guan)溝(gou)隔開,同(tong)時(shi)不(bu)(bu)得妨礙(ai)熱(re)(re)力管(guan)(guan)(guan)道的檢修及地溝(gou)排水。套管(guan)(guan)(guan)應伸出管(guan)(guan)(guan)溝(gou)以外,每(mei)側不(bu)(bu)應小(xiao)于1m。


 ⑧. 熱力網管(guan)溝(gou)(gou)與燃(ran)氣(qi)管(guan)道(dao)交叉當(dang)垂直(zhi)凈距小于300mm時,燃(ran)氣(qi)管(guan)道(dao)應(ying)加套管(guan)。套管(guan)兩端應(ying)超出(chu)管(guan)溝(gou)(gou)1m以上。